CVE-2026-11826CWE-122

OpenPLC_v3 Heap-Based Buffer Overflow in Modbus Master getData()

High · published July 18, 2026

CVSS v4.0
8.7
EPSS
1%
Percentile
54.4
In the wild
Unconfirmed
What it is

OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.

The record
Technical detail
CVSS v4.0
8.7 · HIGH
Vector
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
EPSS
0.00750 · 54.4th percentile
Weakness
CWE-122 · Heap-based Buffer Overflow
Published
2026-07-18T13:35Z
EPSS history
Timeline
  • 18 JUL 13:35Z
    OpenPLC_v3 Heap-Based Buffer Overflow in Modbus Master getData()
    cvelistv5