What it is

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

The record
Technical detail
CVSS v4.0
8.7 · HIGH
Vector
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
EPSS
0.00322 · 24.0th percentile
Weakness
CWE-1287 · Improper Validation of Specified Type of Input
Published
2025-08-14T14:23Z