CVE-2025-3756CWE-1284

CVE-2025-3756

Medium · published April 13, 2026

CVSS v3.1
6.5
EPSS
0%
Percentile
7.6
In the wild
Unconfirmed
What it is

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.

The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.

This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

The record
Technical detail
CVSS v3.1
6.5 · MEDIUM
Vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CVSS v4.0
Not supplied
EPSS
0.00184 · 7.6th percentile
Weakness
CWE-1284 · Improper Validation of Specified Quantity in Input
Published
2026-04-13T22:16Z
References (1)
EPSS history
Timeline
  • 13 APR 17:11Z
    Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850
    cvelistv5