CVE-2024-11499CWE-476
A vulnerability exists in RTU500 IEC 60870-4-104 controlled station functionality, that allows an authenticated and authorized attacker to perform a CMU…
Medium · published March 25, 2025
What it is
A vulnerability exists in RTU500 IEC 60870-4-104 controlled station functionality, that allows an authenticated and authorized attacker to perform a CMU restart. The vulnerability can be triggered if certificates are updated while in use on active connections.
The affected CMU will automatically recover itself if an attacker successfully exploits this vulnerability.
The record
Technical detail
- CVSS v4.0
- 6.9 · MEDIUM
- Vector
- CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/R:A
- EPSS
- 0.00249 · 15.3th percentile
- Weakness
- CWE-476 · NULL Pointer Dereference
- Published
- 2025-03-25T12:30Z
EPSS history
Timeline