CVE-2023-2637CWE-321

Rockwell Automation FactoryTalk System Services Vulnerable To Use Of Hard-Coded Cryptographic Key

High · published June 13, 2023

CVSS v3.1
7.3
EPSS
0%
Percentile
9.7
In the wild
Unconfirmed
What it is

Rockwell Automation's FactoryTalk System Services uses a hard-coded cryptographic key to generate administrator cookies.  Hard-coded cryptographic key may lead to privilege escalation.  This vulnerability may allow a local, authenticated non-admin user to generate an invalid administrator cookie giving them administrative privileges to the FactoryTalk Policy Manger database. This may allow the threat actor to make malicious changes to the database that will be deployed when a legitimate FactoryTalk Policy Manager user deploys a security policy model. User interaction is required for this vulnerability to be successfully exploited.

The record
Technical detail
CVSS v3.1
7.3 · HIGH
Vector
CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:H
CVSS v4.0
Not supplied
EPSS
0.00203 · 9.7th percentile
Weakness
CWE-321 · Use of Hard-coded Cryptographic Key
Published
2023-06-13T20:15Z
EPSS history
Timeline
  • 13 JUN 20:15Z
    Rockwell Automation FactoryTalk System Services Vulnerable To Use Of Hard-Coded Cryptographic Key
    cvelistv5